ZW8-12 Series outdoor high-voltage vacuum circuit breaker

ZW8-12 Series outdoor high-voltage vacuum circuit breaker

ZW8-12 Series outdoor high-voltage vacuum circuit breaker

Product description ZW8-12 series outdoor high-voltage vacuum circuit breaker is a kind of three-phase outdoor high-voltage switchgear of rated voltage 12kV and AC 50Hz.Its population structure is three-phase together box type. Three-phase vacuum arc
Published in2018-08-04
2459 Views

Detailed description

Product description

ZW8-12 series outdoor high-voltage vacuum circuit breaker is a kind of three-phase outdoor high-voltage switchgear of rated voltage 12kV and AC 50Hz.
Its population structure is three-phase together box type. Three-phase vacuum arc-extinguish chamber palaces in a metal cabinet, using the SMC insulating material to insulate inter-phase and phase to earth, which is reliable in performance and high in insulating intensity.

ZW8-12G is combined with ZW8-12 circuit breaker and isolating sword, called combination circuit breaker and used as a section switch.

High-Voltage Vacuum Circuit Breaker (VCB ZW8-12, ZW8-12G)

Main technical data



Item

Unit Parameter
Rated Voltage kV 12
Rated Current A 630
Rated Short-circuit Breaking Current kA 6.3 12.5 20
Rated Short-circuit Making Current (Peak) kA 16 31.5 50
Rated Peak Withstand Current kA 16 31.5 50
Rated Short-time Withstand Current kA 6.3 12.5 20
Rated Insulation Level 1min Power Frequency
Withstand Voltage (Dry Test)
kV 42
Lightning Impulse Withstand Voltage (Peak) kV 75
Rated Operating Sequence O-0.3s-C O-180s-CO
Mechanical Life times 10000
Rated Short-circuit Current Breaking Times times 30
Rated Closing Voltage of Operator V 110, 220
Rated Opening Voltage of Operator V 110, 220
Clearance Between Open Contacts mm 11± 1
Over travel of Contacts mm 3
Three-phase Opening/Closing Synchronization ms ≤ 2
Closing Bouncing Time ms ≤ 2
Average Opening Speed m/s 1.0± 0.2
Average Closing Speed m/s 0.7± 0.15
Opening Time Highest Operating Voltage s 0.015~0.05
Lowest Operating Voltage s 0.03~0.06
Closing Time s 0.025~0.05
Main Loop Resistance of Each Phase μ Ω ≤ 120
Total Thickness of Permissible Wear of Moving and Static Contacts mm 3


Other Similar Products

  • FLW-12/24/40.5 series of Pole mounted SF6 Load break switch

  • LW36-72.5 / 126 Outdoor HV. AC. SF6 circuit breaker

  • ZW30-40.5 Series of outdoor high voltage vacuum circuit breakers

  • ZW20-12 Series outdoor high-voltage vacuum circuit breaker

  • FZW28-12F series AC high voltage demarcation vacuum automatic recloser