ZW8-12 series outdoor high-voltage vacuum circuit breaker is a kind of three-phase outdoor high-voltage switchgear of rated voltage 12kV and AC 50Hz.
Its population structure is three-phase together box type. Three-phase vacuum arc-extinguish chamber palaces in a metal cabinet, using the SMC insulating material to insulate inter-phase and phase to earth, which is reliable in performance and high in insulating intensity.
ZW8-12G is combined with ZW8-12 circuit breaker and isolating sword, called combination circuit breaker and used as a section switch.
Main technical data
Item |
Unit | Parameter | |||||
Rated Voltage | kV | 12 | |||||
Rated Current | A | 630 | |||||
Rated Short-circuit Breaking Current | kA | 6.3 | 12.5 | 20 | |||
Rated Short-circuit Making Current (Peak) | kA | 16 | 31.5 | 50 | |||
Rated Peak Withstand Current | kA | 16 | 31.5 | 50 | |||
Rated Short-time Withstand Current | kA | 6.3 | 12.5 | 20 | |||
Rated Insulation Level |
1min Power Frequency Withstand Voltage (Dry Test) |
kV | 42 | ||||
Lightning Impulse Withstand Voltage (Peak) | kV | 75 | |||||
Rated Operating Sequence | O-0.3s-C O-180s-CO | ||||||
Mechanical Life | times | 10000 | |||||
Rated Short-circuit Current Breaking Times | times | 30 | |||||
Rated Closing Voltage of Operator | V | 110, 220 | |||||
Rated Opening Voltage of Operator | V | 110, 220 | |||||
Clearance Between Open Contacts | mm | 11± 1 | |||||
Over travel of Contacts | mm | 3 | |||||
Three-phase Opening/Closing Synchronization | ms | ≤ 2 | |||||
Closing Bouncing Time | ms | ≤ 2 | |||||
Average Opening Speed | m/s | 1.0± 0.2 | |||||
Average Closing Speed | m/s | 0.7± 0.15 | |||||
Opening Time | Highest Operating Voltage | s | 0.015~0.05 | ||||
Lowest Operating Voltage | s | 0.03~0.06 | |||||
Closing Time | s | 0.025~0.05 | |||||
Main Loop Resistance of Each Phase | μ Ω | ≤ 120 | |||||
Total Thickness of Permissible Wear of Moving and Static Contacts | mm | 3 |